Performance of Single Pass Earth-Tube Heat Exchanger: An Experimental Study

Authors

  • Girja Sharan Coordinator, Cummins-IIMA Lab, Centre for Mgt in Agriculture, Indian Institute of Management, Ahmedabad. Author
  • Ratan Jadhav Project Officer, SEWA, Ahmedabad, Gujarat, India Author

DOI:

https://doi.org/10.52151/jae2003401.1021

Abstract

A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating modes. ETHE consisted of 50 m mild steel pipe of 10 cm nominal diameter and 3 mm wall thickness, buried 2.85 m deep below ground. Ambient air was pumped through it for conditioning. Tests were conducted on three consecutive days in each month. The ETHE conditioned 5.6 m3/min of 40.6°C air to 26.6°C in cooling mode, and 8.3°C air to 23.0°C in heating mode. Average COP was 3.3 in cooling and 3.8 in heating mode.

Downloads

Download data is not yet available.

References

ASHRAE 1985. Handbook of application. Atlanta Ga. American Society of Heating Refrigerating and Air Conditioning engineers Inc.

Baxter DO 1992. Energy exchange and related temperature of an eartb-tube heat exchanger in heating mode. Trans ASAE 35 (1) : 275-285.

Baxter DO 1994. Energy exchange and related temperature of an earth-tube heat exchanger in cooling mode. Trans ASAE 37 (1) : 257-267.

Goswamy DY; Dhaliwal AS 1985. Heat transfer analysis in environmental control using an underground air tunnel. Journal of Solar Energy Engineering 107 : 141-145.

PuriVM 1986. Feasibility and performance curves for intermittent earth-tube heat exchangers. Trans ASAE 29 (2) : 526-532.

Santamouris M; Mihalakaha G; Balaras CA; Argirioua Asimakopoulos D; Vallinaras M 1995. Use of Buried pipes for energy conservation in cooling of agricultural greenhouse. Solar Energy 35:111-124

Sawhnay RL; Budhi D; Thanu NM 1998. An experimental study of summer performance of a recirculation type underground air-pipe air conditioning system, Building and Environment 34 189-196.

Scott"NR; Parsons RA; Koehler TA 1965. Analysis and performance of an earthtube heat exchanger. ASAE paper no. 65840 St. Joseph, Michigan, ASAE.

Sharan G; Jadhav R 2002. Soil temperature regime at Ahmedabad. J Agril Engng 39 (1) : 27-32.

Sharan G; Sahu RK; Jadhav R 2001. Earth-tube heat exchanger based air-conditioning for tiger dwellings. Zoos' Print 16 (5) May (RNI2:8).

Spengler R. W. and Stombaugh D.P 1983. Optimization of earth-tube heat exchanger for winter ventilation of swine housing. Trans ASAE 26 : 1186-1193.

Published

2003-03-31

Issue

Section

Regular Issue

How to Cite

Girja Sharan, & Ratan Jadhav. (2003). Performance of Single Pass Earth-Tube Heat Exchanger: An Experimental Study. Journal of Agricultural Engineering (India), 40(1), 1-8. https://doi.org/10.52151/jae2003401.1021